PR, CUF and specific yield: how to read a solar plant's numbers
Three numbers tell you most of what you need to know about a solar plant: performance ratio (PR), capacity utilisation factor (CUF) and specific yield. Here is what each one means, how to calculate it, and what a healthy value looks like in India.
Specific yield
Specific yield is the energy a plant produced for each kilowatt-peak of panels installed. It lets you compare plants of different sizes.
A clean, well-oriented plant in most of India gives roughly 3.5 to 4.8 kWh/kWp on a clear day, and about 1,300 to 1,650 kWh/kWp over a year. Rajasthan and Gujarat sit at the high end; the north-east and hilly regions sit lower.
Performance ratio (PR)
PR tells you how much of the sunlight that reached the panels became electricity, after all losses. Because it divides out the weather, it is the best single measure of plant health.
Insolation comes from an irradiance sensor (pyranometer) at the site. 1 kWh/m² of sunlight on 1 kWp of panels would ideally produce 1 kWh, so a PR of 78% means 22% was lost to heat, dust, wiring, inverter conversion and downtime.
| PR | What it usually means |
|---|---|
| Above 80% | Healthy, clean plant |
| 72 to 80% | Normal, with summer heat losses |
| 60 to 72% | Soiling, shading, a tripped string or an inverter fault is likely |
| Below 60% | A significant fault. Check the inverters and strings today |
Capacity utilisation factor (CUF)
CUF compares what the plant produced with what it would have produced running at full capacity around the clock.
Because the sun sets every day, solar CUF in India is usually 16 to 21%. CUF is useful for comparing with targets in power purchase agreements, but unlike PR it moves with the weather, so a cloudy month lowers CUF even when the plant is healthy.
Expected vs actual generation
The most practical daily check is to compare actual energy with the energy the plant should have made in the sunlight it received:
If actual energy stays below about 80% of expected on a sunny afternoon, something is wrong. If one inverter's specific yield is 15% or more below the others at the same site, the problem is in that inverter's strings, MPPT or panels, not the weather.
How SolarPulse uses these numbers
SolarPulse calculates PR, CUF and specific yield for every site from inverter and weather-station data every five minutes. It draws expected power next to actual power on each site's chart and raises a fault when a plant or a single inverter falls behind, so your team can act the same day.